NHẬN DẠNG MÔ HÌNH TUYẾN TÍNH THAM SỐ BIẾN THIÊN HỘP XÁM CHO NHIỆT ĐỘ HƠI QUÁ NHIỆT CỦA LÒ HƠI
Keywords
Abstract
This paper focuses on the identification of grey-box LPV model for the boiler superheated steam temperature from local approach. Rather than building a model either from the law of physics or from experimental data independently, the combination of an analytic and an experimental approach is used to identify an LPV model of a boiler superheated steam temperature. The parameters of the LPV model are approximated as a rational function of the main steam flow. The global LPV model is estimated by applying a parameters interpolation technique of local linear model parameters. The proposed method is applied to the identification for Boiler superheated steam temperature process in the Pha-Lai Power Plant. The results show that the obtained model is of high accuracy and the proposed method is feasible.